\mainpage Open62541 Developer Documentation
OPC UA (short for OPC Universal
Architecture) is a protocol for industrial communication and has been standardized in the IEC62541.
At its core, OPC UA defines a set of services to interact with a server-side object-oriented
information model. Besides the service-calls initiated by the client, push-notification of remote
events (such as data changes) can be negotiated with the server. The client/server interaction is
mapped either to a binary encoding and TCP-based transmission or to SOAP-based webservices. As of
late, OPC UA is marketed as the one standard for non-realtime industrial communication.
We believe that it is best to understand OPC UA *from the inside out*, building upon conceptually
simple first principles. After establishing a first understanding, we go on explaining how these
principles are realized in detail. Examples are given based on the *open62541* implementation of the
standard.
OPC UA, a collection of services
--------------------------------
In OPC-UA, all communication is based on service calls, each consisting of a request and a response
message. Be careful to note the difference between services and methods. Services are pre-defined in
the standard and cannot be changed. But you can use the *Call* service to invoke user-defined
methods on the server.
For completeness, the following tables contain all services defined in the standard. Do not bother
with their details, yet. We will introduce the different services later in the text. In open62541,
each service is implemented in a single function. See the \ref services section for details.
__Establishing communication__
| Discovery Service Set | SecureChannel Service Set | Session Service Set |
|-----------------------|---------------------------|---------------------|
| FindServers | OpenSecureChannel | CreateSession |
| GetEndpoints | CloseSecureChannel | ActivateSession |
| RegisterServer | | CloseSession |
| | | Cancel |
__Interaction with the information model__
| NodeManagement Service Set | View Service Set | Query Service Set | Attribute Service Set | Method Service Set |
|----------------------------|--------------------------------|-------------------|-----------------------|--------------------|
| AddNodes | Browse | QueryFirst | Read | Call |
| AddReferences | BrowseNext | QueryNext | HistoryRead | |
| DeleteNodes | TranslateBrowsePathsToNodeIds | | Write | |
| DeleteReferences | RegisterNodes | | HistoryUpdate | |
| | UnregisterNodes | | | |
__Notifications__
| MonitoredItem Service Set | Subscription Service Set |
|---------------------------|--------------------------|
| CreateMonitoredItems | CreateSubscription |
| ModifyMonitoredItems | ModifySubscription |
| SetMonitoringMode | SetPublishingMode |
| SetTriggering | Publish |
| DeleteMonitoredItems | Republish |
| | TransferSubscription |
| | DeleteSubscription |
OPC UA, a web of nodes
----------------------
The information model in each OPC UA server is a web of interconnected nodes. There are eight
different types of nodes. Depending on its type, every node contains different attributes. Some
attributes, such as the *NodeId* (unique identifier) and the *BrowseName*, are contained in all node
types.
ReferenceTypeNode | MethodNode |
DataTypeNode | ObjectTypeNode |
VariableTypeNode | ObjectNode |
VariableNode | ViewNode |
Nodes are interconnected by directed reference-triples of the form `(nodeid, referencetype,
target-nodeid)`. Therefore an OPC UA information model is easiest imagined as a __web of nodes__.
Reference types can be
- standard- or user-defined and
- either non-hierarchical (e.g., indicating the type of a variable-node) or hierarchical (e.g., indicating a parent-child relationship).
OPC UA, a protocol
------------------
The OPC UA protocol (both binary and XML-based) is based on 25 *built-in* datatypes. In open62541, these
are defined in ua_types.h.
Boolean | Float | StatusCode |
SByte | Double | QualifiedName |
Byte | String | LocalizedText |
Int16 | DateTime | ExtensionObject |
UInt16 | Guid | DataValue |
Int32 | ByteString | Variant |
UInt32 | XmlElement | DiagnosticInfo |
Int64 | NodeId | |
UInt64 | ExpandedNodeId | |
The builtin datatypes are combined to more complex structures. When the structure contains an array,
then the size of the array is stored in an Int32 value just before the array itself. A size of -1
indicates an undefined array. Positive size (and zero) have the usual semantics.
Most importantly, every service has a request and a response message defined as such a data
structure. Their exact definitions can be looked up here:
https://opcfoundation.org/UA/schemas/Opc.Ua.Types.bsd.xml. In open62541, we autogenerate the
C-structs to handle the standard-defined structures automatically. See ua_types_generated.h for
comparison. The entire OPC UA protocol revolves around the exchange of these request and response messages.
*/